Network 15/06/2012 downtime explanation

Our report from the incident on 15/06/2012 is as follows.
 
Issue

Complete loss of all connectivity to our entire network

Underlying cause

Our upstream transit provider’s switch failed at Reynolds House, Manchester, causing the loss of connectivity on one site feed. Simultaneously, a power breaker failed at Delta House, Manchester, rendering the redundant feed unavailable too.

Symptoms

Complete loss of all connectivity to our entire network

Resolution

A temporary alternative transit feed has been provisioned and routes are now sent via this (around 3 hops more than the previous feed). This is a semi-permanent fix whilst the switch is replaced in Reynolds House. There is expected to be planned maintenance to change the transit back to the primary feed; but nothing has been scheduled yet. The network is now operating as it should be and we apologise for the downtime. Downtime incurred was 180 minutes.

Network Connectivity partially restored

Routes are now being sent over alternative carriers and connectivity is partially restored.

Network Complete loss of network connectivity

The root cause of the fault has been identified as a breaker failure, resulting in some racks in the data centre losing power.

Whilst all our racks still have power, the routing equipment providing connectivity does not.

Engineers are on site working on two solutions simultaneously.

  1. They are repairing the failed breaker to restore power to the routing racks
  2. An alternative upstream link is being rapidly set up to restore connectivity in the interim.

We apologise for this incident and downtime thus far and will provide future updates here.

Network Complete loss of network connectivity

Our upstream provider has had a complete loss of connectivity at our primary data centre and it is currently being investigated.

At this stage, the reason for the fault is unknown

More information will follow when it is available.